NS300/NS500 Maximum Feed Speed Parameter Pn843 Technical Supplement
This technical supplement explains that if the maximum feed speed parameter Pn843 is set below other speed-related parameters, the Module Reset Function will fail to save data to non-volatile memory on NS300 or NS500 modules, and no alarms or warnings will be issued. It lists all parameters that must be set below the Pn843 value, including their configuration utility locations and EDS sheet equivalents, and warns that most speed-related parameters default to 24,000.