80 Series Drives Run Time in Hours Technical Note
AI-enhanced description
This technical note explains how to calculate and display drive run time in hours instead of the default days, using the On-Time counter in Group 33 and an adaptive program. It describes setting parameter 33.13 to count seconds when the drive is modulating, then dividing by 3600 and storing the result in a DataStorage location for PLC access via Fieldbus.